The circuit breaker is one of the most important protective electrical components in an electrical installation. Its function is to automatically cut off the flow of current when an overload or short circuit occurs, thereby preventing excessive current from damaging the conductors and connected equipment.
Understanding the parts of a circuit breaker enables you to understand how it works, why it trips and what features should be taken into account when selecting a suitable device.
In this article, we explain its internal and external components, how its protection systems work and what differences exist between the main types of circuit breakers.
Table of Contents
What is a circuit breaker?
A circuit breaker is an electrical protection device designed to cut off the power supply when it detects an overcurrent that could compromise the safety of the circuit.
It is also known as a thermal-magnetic circuit breaker or MCB (Miniature Circuit Breaker) when referring to small, modular devices.
Its operation combines two independent protection systems that act on a common tripping mechanism.
The first is the thermal system, which detects overloads that persist for a certain period of time. The second is the magnetic system, which responds rapidly to very high currents, generally associated with short circuits.
This combination protects the conductors against two different situations:
- Electrical overload: this occurs when the current exceeds the circuit’s rated capacity for a period long enough to cause dangerous overheating.
- Short circuit: this occurs when a very low-impedance connection is established between points with different potentials, usually causing a sudden surge in current.
In domestic installations, circuit breakers are usually found in the fuse box, where they provide individual protection for different circuits, such as lighting, sockets or certain household appliances.
Unlike a fuse, which must be replaced after it has tripped, a circuit breaker can be reset once the cause of the trip has been rectified, provided the device is in good working order.
It is important not to confuse circuit breakers with residual current devices (RCDs), as they fulfil different protective functions. Whilst circuit breakers act in the event of overloads and short circuits, RCDs detect specific residual or leakage currents. Furthermore, there are different classes of residual current devices depending on the currents they can detect, as explained in our article on the differences between Type A and Type AC residual current devices.
Recommended products

In Stock, delivery in 15-20 days
21.99 £
Residential Differential Circuit Breaker 2P 30mA 25-40A 6kA Class AC LEGRAND RX³ 402056
View product

In Stock, delivery in 15-20 days
13.69 £
MiBoxer LED Pushbutton to Relay Switch Circuit Breaker Converter
View product
What are the parts of a circuit breaker?
A circuit breaker consists of various mechanical and electrical components that allow current to flow under normal conditions and cut it off in the event of a fault.
Although their design may vary depending on the manufacturer, the number of poles and the device’s specifications, conventional modular circuit breakers share a similar internal structure.
1. Insulating casing
The casing is the outer structure that houses and protects the internal components of the circuit breaker.
It is generally manufactured from insulating thermoplastic materials that offer mechanical strength, thermal stability and suitable fire-resistance properties.
Its function is to keep the conductive parts separate, provide electrical insulation and protect the mechanism from external agents under the intended conditions of use.
Furthermore, it allows the device to be integrated into the electrical panel and makes it easier to identify by means of the manufacturer’s markings.
The casing must not show any cracks, deformations or signs of overheating. Any visible damage may indicate a problem requiring professional inspection.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
2. Operating lever
The lever is one of the most visible parts of the circuit breaker and allows the circuit to be opened or closed manually.
It usually has two positions, identified by the symbols I (on) and O (off).
When set to the ‘on’ position, the mechanism keeps the electrical contacts closed, allowing current to flow. When moved to the ‘off’ position, the contacts separate and the circuit is broken.
However, the lever alone does not determine the operation of the protective devices.
Circuit breakers incorporate a trip mechanism that allows the contacts to open automatically when a fault is detected, even if an attempt is made to manually hold the lever in the ‘on’ position.
Some models also feature an intermediate position or specific indicators to signal that a trip has occurred.
3. Fixed and moving electrical contacts
Electrical contacts are the components responsible for physically allowing or interrupting the flow of current.
In a conventional circuit breaker, there are fixed contacts and moving contacts which remain in contact when the circuit is closed.
During normal operation, current flows through these elements and the device’s other conductive components.
When a sufficiently prolonged overload or a short circuit occurs, the trip mechanism causes the contacts to separate.
This separation must take place with the speed and at the distance necessary to interrupt the current in accordance with the circuit breaker’s characteristics.
The contacts are made from materials suitable for withstanding the electrical and thermal stresses associated with opening and closing operations.
4. Bimetallic strip or thermal release
The bimetallic strip is the main component of the circuit breaker’s thermal protection system.
It consists of two metals joined together which have different coefficients of thermal expansion.
When an electric current flows, the heat generated by the current causes the strip to deform progressively.
If the current exceeds certain values for a sufficient length of time, the deformation triggers the trip mechanism and causes the circuit to open.
This system is particularly useful for detecting sustained electrical overloads.
The thermal response is not necessarily immediate. Its response time depends on the current flowing, the trip characteristic and the thermal conditions of the device.
For example, a small overcurrent may take longer to trigger the device than a much larger overload.
This characteristic prevents unnecessary tripping in the event of certain transient current variations.

ⓘ Illustrative contextual content generated or edited using AI (Section 50 of the AI Act).
5. Electromagnetic coil or magnetic trigger
The electromagnetic coil forms part of the short-circuit protection system.
When current flows through the coil, it generates a magnetic field whose strength increases with the current flowing through it.
Under normal conditions, this field does not cause the mechanism to operate.
However, when a sufficiently high current is present, the electromagnetic force displaces a core or a moving armature, which releases the trigger mechanism.
As a result, the contacts open rapidly and the current is interrupted.
Unlike the thermal trip unit, the magnetic trip unit is designed to operate without any intentional delay when the current reaches its operating range.
The trip threshold depends on the circuit breaker’s trip curve, which means that not all circuit breakers respond in exactly the same way to the same current.
6. Arc-extinguishing chamber
The arc-extinguishing chamber is an essential component that enables the circuit breaker to safely interrupt high currents.
When the electrical contacts separate whilst current is flowing, an electric arc may form between them.
This arc consists of a discharge through an ionised medium and can reach very high temperatures.
To control this, the circuit breaker incorporates a chamber usually consisting of a set of metal plates that help to split, cool and extinguish the arc.
The internal geometry of the device allows the arc to move into this chamber during opening.
Its design directly influences the circuit-breaker’s ability to interrupt short-circuit currents without sustaining damage that would render it unfit for its intended operation.
For this reason, the arc-quenching chamber is one of the elements that must be taken into account when assessing the performance of a circuit breaker.
7. Trip mechanism and springs
The trip mechanism coordinates the opening and closing of the electrical contacts.
It consists of various mechanical components, such as internal levers, interlocks, springs and transmission parts.
Under normal conditions, it keeps the contacts closed whilst the switch remains switched on.
When the thermal or magnetic trip unit detects a fault, it releases the mechanism, allowing the energy stored in the springs to cause the contacts to open rapidly.
This system ensures that disconnection does not depend solely on the speed at which the external lever moves.
It also allows the switch to be reset after tripping, provided that the problem has been resolved and there is no damage to the device.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
8. Connection terminals
Terminals are the points that allow electrical conductors to be connected to the circuit breaker.
They are usually located at the top and bottom of the device and may incorporate different connection systems, such as screw terminals or push-in connectors.
Their function is to ensure a proper electrical and mechanical connection between the circuit breaker and the circuit’s conductors.
An incorrect connection can increase contact resistance and lead to localised overheating, deterioration of the insulation or malfunctions.
It is therefore important to follow the manufacturer’s instructions regarding conductor cross-section, terminal type, tightening torque and connection position.
The installation and handling of these components must be carried out by qualified personnel, in accordance with the relevant safety requirements.
How does a circuit breaker work?
A circuit breaker operates by indirectly monitoring the current flowing through the circuit via its thermal and magnetic components.
When the current remains within the specified limits, the contacts remain closed and the power supply continues as normal.
If an overcurrent occurs, the device can operate via two different mechanisms.
Operation in the event of an overload
An overload occurs when the current flowing through a circuit exceeds the permissible values for a certain period of time.
This can occur, for example, when several appliances are switched on simultaneously and their combined load exceeds the circuit’s rated capacity.
In this situation, the bimetallic strip gradually heats up.
When it reaches the required degree of deformation, it triggers the trip mechanism and causes the circuit to be disconnected.
The response time depends on the magnitude of the overload and the device’s time-current curve.
Therefore, a circuit breaker does not necessarily trip immediately when the current slightly exceeds its rated value.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
Operation in the event of a short circuit
A short circuit can generate a current considerably higher than that during normal operation.
When this current reaches the magnetic trip threshold, the coil causes the opening mechanism to release rapidly.
The contacts separate and the arc-quenching chamber is activated to control the electric arc generated during the interruption.
This assembly helps to limit the effects of the fault current, provided that the device’s breaking capacity and operating conditions are not exceeded.
The speed of response is particularly important because short-circuit currents can cause high thermal and electrodynamic stresses in the conductors and components of the installation.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
Technical characteristics of a circuit breaker
As well as understanding its internal components, it is important to interpret the specifications marked on the circuit breaker’s casing.
This information enables you to identify its performance characteristics and check that it is suitable for a particular installation.
Rated current
The rated current, denoted by In, indicates the current value assigned to the device under the specified reference conditions.
Modular circuit breakers are available in various rated currents, such as 10 A, 16 A, 20 A, 25 A or 32 A, amongst others.
However, the choice should not be based solely on the power rating of the connected equipment.
The conductor cross-section, its permissible current-carrying capacity, the installation method, environmental conditions and regulatory requirements must also be taken into account.
A circuit breaker with an excessively high rated current may not provide adequate protection for the wiring.
Trip curve
The tripping curve describes the relationship between the current flowing through the circuit and the time required to trigger disconnection.
In modular circuit-breakers, some of the most common curves are:
| Curve | Magnetic trip range | Indicative applications |
| B | 3 to 5 times In | Circuits with low inrush currents |
| C | 5 to 10 times In | General installations and certain loads with moderate starting conditions |
| D | 10 to 20 times In | Loads with high starting currents, where the installation design permits |
These ranges relate to magnetic tripping and should not be confused with thermal protection thresholds.
The selection of the curve must also take into account the available short-circuit current and the conditions required to ensure disconnection.
Breaking capacity
Breaking capacity is the ability of a circuit breaker to interrupt a short-circuit current under specified conditions.
In low-voltage installations, thermal-magnetic circuit breakers with different breaking capacities may be found, such as 4 kA, 4.5 kA, 6 kA or 10 kA, depending on the model, the applicable standard and the characteristics of the installation.
This rating must be suitable for the expected short-circuit current at the point where the device is installed.
The breaking capacity, normally expressed in kiloamperes, must not be confused with the rated operating current, expressed in amperes.
Types of circuit breakers according to their number of poles
Circuit breakers can also be classified according to the number of poles and the configuration of the conductors they are designed to interrupt.
This classification applies specifically to circuit breakers, although there are other types of electrical switches that perform different functions within an installation, such as the manual control of circuits or the operation of lighting systems.
Single-pole switches and 1P+N
Single-pole circuit breakers (1P) have a single pole protected against overloads and short circuits, generally intended for the live wire.
Meanwhile, 1P+N models incorporate two poles that are disconnected together: one for the phase and the other for the neutral. Usually, overcurrent protection is only provided on the phase pole, whilst the neutral has a disconnection mechanism.
Both configurations can be used in single-phase installations, although the choice depends on the circuit’s protection and isolation requirements.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
Two-pole switches
Bipolar (2P) circuit breakers have two poles that are operated simultaneously, enabling both conductors in the circuit to be disconnected.
Unlike conventional 1P+N models, bipolar circuit breakers usually incorporate thermal and magnetic protection on both poles.
They are used in circuits that require this protection configuration, always in accordance with the characteristics of the electrical installation.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
Three-pole and four-pole circuit breakers
Three-pole (3P) circuit breakers have three poles and are mainly used to protect three-phase circuits without a neutral, such as certain power supply circuits for motors and industrial machinery.
Four-pole (4P) circuit breakers, on the other hand, have four poles and allow the three phase conductors and the neutral to be disconnected simultaneously in three-phase installations where this is required.
Depending on the model, four-pole devices may incorporate overcurrent protection on all four poles or have a neutral pole without thermal and magnetic protection.
The selection of each configuration must be made taking into account the characteristics of the mains supply, the conductors and the circuit’s protection requirements.

ⓘ Illustrative contextual content generated or edited using AI (Art. 50 AI Act).
The importance of the circuit breaker in an electrical installation
Knowing the parts of a circuit breaker and understanding how it works is essential to understanding how an electrical installation is protected against overloads and short circuits. Each of its components performs a specific function that helps to ensure proper disconnection when these situations occur. Furthermore, factors such as the rated current, the trip curve, the breaking capacity and the number of poles are crucial in selecting the most appropriate device. Therefore, choosing a circuit breaker suited to the characteristics of each circuit and ensuring it is installed correctly is essential for maintaining the safety and proper functioning of the electrical system.